Blowdown Separators
Blowdown Waste Management
The HBC Blowdown Separator is designed to take water from the boiler during blowdown and reduce it to atmospheric pressure for disposal. The HBC Separator accomplishes this by separating the subsequent flashed steam from the hot water. As the blowdown enters the vessel, it is forced into a centrifugal pattern by means of a striking plate. The steam is vented to the atmosphere through a top connection. The HBC Separator is built as per requirements Section VIII of the ASME Code and stamped by the National Board of Pressure Vessel Inspectors. The HBC Blowdown Separator provides an economical means of safe boiler blowdown.

The separator includes a structural steel support stand for mounting to foundation. Options available are after cooler, manual cooling valve assembly, automatic cooling valve assembly, and exhaust heads.

Hurst Blowdown Separators are built to Section VIII, Division 1 of the ASME Code for 250 PSI design pressure. (200 PSI design pressure with 150# ANSI flanges) Blowdown separator design pressure should be a minimum of 25% of the boiler maximum allowable working pressure (MAWP) as recommended by the National Board.

Designed, constructed and stamped in accordance with
the requirements of the ASME Boiler Codes.




SPECIFICATIONS (ALL DIMENSIONS ARE IN INCHES)
  BOILER TAIL PIPE DIMENSION 3/4 - 1 1/2
ECONOMY
3/4 - 1 1/2
BLOWDOWN
1/14
BLOWDOWN
1 1/2 - 2
BLOWDOWN
2 - 2 1/2
BLOWDOWN
  BDS. MODEL NUMBER BDS8 (SEE NOTE 1) BD14X24 BD14X34 BD14X34A BD14X56
A TANK DIAMETER 8 14 14 14 14
B LENGTH 26 24 34 34 56
C DRAIN TO FLOOR 16 24 24 24 24
D OVERALL HEIGHT 42 48 60 58 1/4 80
E INLET SIZE 1 1/4 1 1/2 1 1/4 2 2 1/2
F INLET LENGTH 3 3 1/2 3 1/2 3 1/2 3 1/2
G OVERALL RADIUS 7 1/2 10 7/8 10 7/8 10 7/8 10 7/8
H VENT & DRAIN 2 1/2 2 1/2 3 4 6
I LENGTH W/FLG. 32 1/2 30 1/2 40 40 62
J FLANGE TO FLOOR 13 21 21 21 21
  WEIGHT NET/SHIPPING LBS. 80/100 180/200 225/255 225/256 355/395
NOTE: 8” DIAMETER SEPARATORS ARE DESIGNED FOR BOILERS NEEDING SHORT DURATION BLOWDOWN ONLY. (SUCH AS VERTICAL TUBELESS BOILERS) • DIMENSIONS SUBJECT TO CHANGE WITHOUT NOTICE, CERTIFIED DRAWINGS AVAILABLE UPON REQUEST • THREADED VENT & DRAIN STANDARD, FLANGED OPTIONAL.